No Instruction boiler sime friendly format 80e and boiler stoped working?Hi, I moved recently to a new flat where I have sime friendly format 80e boiler. I do not have instruction for my boiler sime friendly format 80e. The pressure is zero an dcan not light the ignation light. can you help me please.
Maliha March 2006
|
|
|
Click here if you can answer this question |
|
|
|
|
|
if you wish i i have a user guide, and don't mind either copying it and posting it or faxing it to you, or even scanning it and emailing it to you,
kerrie October 2006 |
|
|
|
|
|
|
|
|
hi, the 80e is a very easy boiler to repair. first fill up the system via the cold water filling loop to a pressure of around
1.25 bar on the gauge, check the gas is turned on,set the boiler to winter setting or summer setting, turn the hot water to max, and the heating to max, the boiler will now start ie the fan will run, the pump will run,and the boiler will light up. this boiler does not have a pilot light it fires up via a spark generator via the pc board,please let me know how you get on any problem and i will send you a copy of the manual.bobby rob. ps do not play with gas[bang]and make sure the time clock is not stopping it from running.
bobby rob May 2006 |
|
|
|
|
|
|
|
|
I'm Sure if you call Johnston boilers in srathaven, they will be the very chaps that will be able to help you. they work with sime boilers.
shaun March 2006 |
|
|
|
|
|
|
|
|