Vaillant eco max 835/2e .....F25 recurring?Having had a qualified corgi boiler fitter come round to look at our combi,we have the same problem over & over.
The boiler continually loses pressure despite having a new water switch,expansion vessel adjustment,a magnetic cleaner fitted to the system & a negative air compression test for leaks in the system.??
Even the plumber is baffled about this case .
Anybody out there have any ideas please?
We are a frozen family of 4!
Cheers in advance.
Steve October 2010
|
|
|
Click here if you can answer this question |
|
|
|
|
|
All seem to be working.
Still f25 recurring
Steve October 2010 |
|
|
|
|
|
|
|
|
Just remembered something, on the many hundreds of Ecomax's I have worked on I have had this situation only ONCE before.
Pressure up the boiler, then turn everything OFF, check the condense outlet, if it's running water (even a trickle) you have an internal split in the main heat exchanger passing through the condense waste. I remember going through all the same processes it sounds as though you have been through.
Unusual scenario I appreciate, but I just remembered and thought it might be useful to you, hope it helps.
Carefree October 2010 |
|
|
|
|
|
|
|
|
Has the prv been changed?
Also although the expansion vessel has been changed, was it checked for air pressure charge when it was installed? And check for a block on the expansion tube pipe.
I must admit, you buy a new vessel and install it, you would trust it to be charged, twice (with two manufacturers) I have been caught out with this.
Carefree October 2010 |
|
|
|
|
|
|
|
|